TC Spec. AWWA-D100
FACTORY-WELDED SPECIFICATION FOR
POTABLE WATER STORAGE
GENERAL
The Engineer's
selection of factory-welded (factory-coated carbon steel) (stainless steel)
(aluminum) tank construction for this facility has been predicated upon the
design criteria and construction methods specified. Deviations from the
specified design and construction details will not be permitted.
DRAWINGS
AND SPECIFICATIONS
After receipt
of order, the Vendor is required to furnish, for the approval of the
Engineer, complete specification and construction drawings for all work
shown on the bid drawings. When approved, one set of such prints will be
returned to the Vendor marked Approved, and these drawings will
govern the work detailed. The approval by the Engineer of the Contractor's
drawings shall be an approval relating only to their general conformity with
the bid drawings and specifications.
The Owners
drawings and specifications showing general dimensions and construction
details shall govern construction. After approval by the Engineer of
detailed drawings prepared by the Vendor, there shall be no deviation from
the drawings and specifications except upon written order or approval from
the Engineer.
QUALIFICATION OF BIDDER
The Bidder
shall be a specialist in the design and fabrication of factory-welded carbon
steel, stainless steel, and aluminum tanks. Bidder shall also submit, upon
request, a list of five comparable tanks now in service in the United States
for references.
I. General
Information
-
Buyer's name:
_________________________________________________
-
Jobsite location: City __________, State __________ Zip Code
__________
-
Liquid stored in tank: ______________
-
Specific gravity of product: _________
-
pH of product: __________
-
Temperature: __________ degrees
-
Nominal capacity: __________ gallons
-
Maximum liquid depth: __________ feet
-
Minimum freeboard: __________ inches
-
Suggested tank geometry: Diameter __________ Eave height
__________
-
Design pressure: (std. CS 14.0, SS 10.0, AL 6.0 oz.) (other
__________)
-
Design vacuum: (std. CS 1.0, SS 1.0, AL 0.6 oz.) (other
__________)
-
Roof live load: __________ PSF
-
Seismic Zone per AWWA D100
-
Wind design per AWWA D100
-
Material of construction: (carbon steel)(stainless steel;
304/316L)(aluminum 5052)
II. Scope of
Supply
A.
Furnish all material necessary for the tanks and appurtenances
specified.
B.
Tanks will be designed to be self-supporting on customer-supplied
foundation.
C.
Delivery will be accomplished on specialty trailer equipment. Actual
transportation equipment will be dictated by tank geometry.
D.
Welded tank installation services at the jobsite will be optional at
customer request.
III. Design Criteria
A. Vendor to
quote on the nearest standard size welded tanks of manufacturer.
B. Standard
wind design is 100 MPH wind velocity using AWWA D100-96 as a
reference.
C. Seismic
design (if applicable) is to be based on AWWA D100-96. When
designing a tank in a seismic zone, the load producing the higher stresses
comparing wind and seismic will control the dynamic portion of design.
D. Combined
live and dead roof load shall be uniformly distributed with all nozzle,
manhole, and filter locations designed for a minimum of 200 lbs. each. Live
and dead loads to be a combined minimum of 25 psf. Roof to have 10o
(2.116 to 12) slope for water drainage. Roof is typically not designed as a
working platform.
E. Tank
design to be based on a level full capacity using specific gravity of the
product.
F. Owner
solicits recommendations that may improve the price, delivery, or
performance of tanks. As an alternate, Vendor is invited to quote changes in
physical dimensions, modifications to the design, fabrication, or stock of
Vendor's standard equipment that would reduce the initial cost of the
equipment as specified without changing the design premise.
Alternate
quotations shall be listed as such in the proposal specifying the alternate
and the price and delivery for the alternate.
IV.
Material Specifications
A.
Shell Structure
The materials, design, and
fabrication of the welded shell shall conform to the manufacturer's standard
specifications including the following:
1.
Materials Carbon Steel
a.
Hot Rolled Sheet and Plate - ASTM A570 Grade 40 or equal with a
minimum yield strength of 40,000 psi. Minimum thickness shall be 10 gauge.
b.
Structural Shapes - Carbon steel structural shapes shall conform to
ASTM A36 or ASTM A992.
c.
Pipe - Carbon steel structural pipe shall conform to ASTM A53 GR. B
2.
Materials Stainless Steel & Aluminum
a.
Aluminum - 5052-H32, 6061-T6 typical grades
b.
Stainless steel - 304, 304L, 316L, typical grades
c.
Other grades of carbon steel, stainless steel and aluminum are
available.
3. Bolts
a.
Bolts shall be 1/2 inch diameter and shall meet or exceed the
requirements of AWWA D100-96. Standard bolt coating is mechanically
galvanized per ASTM B695, Class 50.
b.
Anchor bolts conform to ASTM A36 or A307. Anchor bolt to shell
connections shall be bolted to allow for fabrication and shipping
efficiency.
c.
Other bolts shall meet or exceed ASTM A307 or ASTM325.
4. Gaskets
a. Bolted
connections shall incorporate white EPDM gasket material.
B.
Manufacturing
-
Welding - All structural welding shall be to the latest
edition of AWS using ASME or AWS certified welders - AWS D1.2 for
aluminum, AWS D1.1 for carbon and stainless steel. Welding procedures
are qualified to ASME Section IX.
-
Shell seams shall be full penetration using the SAW (sub-arc
welding) process with copper backup.
-
Other seams may be made with GMAW (gas metal arc welding),
SMAW (shielded metal arc welding), FCAW (flux-cored arc welding) or SAW
(submerged arc welding) process.
C. Coatings Applicable to carbon steel only
D. Appurtenances/Accessories
Standard Accessories
- 20
center roof dome with cover plate
-
Lifting hauling lugs as required by tank design
- 24
Square roof hatch
- 20
Diameter shell manway
-
Foundation loads
-
Foundation anchor bolts and clips
Optional Accessories
-
Specify - Stub and flanged nozzles required in deck, sidewall, and hopper
-
Specify Level indicator gauge
-
Complete overflow pipe assembly with internal weir cone
-
Specify - Special hopper outlet size or configuration required
- Deck
perimeter guardrail with toeboard (OSHA)(aluminum rails, hot-dip galvanized
posts)
-
Outside ladder with safety enclosures and rest platforms (OSHA), hot-dip
galvanized with aluminum rest platform
-
Crossovers for access between tanks (OSHA)(aluminum rails, bargrate
material, hot-dip galvanized posts)
V. Shipping
-
All tanks, structures, and miscellaneous parts shall be
packaged for shipment in such a fashion as to minimize abrasion or
scratching of finished coating sys
-
Shipment by special trailers designed for hauling
tank/cylinder shapes.
-
Shipping covers shall be provided for all openings.
VI. End of
Specification (Section B Coating specification attached)
TC Coating Spec. AWWA D100 Section
B
I.
Surface Preparation
A.
An SSPC-SP6 (commercial) blast surface profile is required for the
coatings listed.
B.
Blasted surface profile will not be exposed to rain, dew or other
contaminants prior to coating application.
II.
Interior Coatings
A.
Immersion Bond Epoxy immersion liquid application
·
Two coats of NSF approved amine epoxy, spray applied at 8 mils
DFT average total.
B.
No internal coating required
C.
Special field applied coating to be specified
III. Exterior Coatings
A.
Polyamide Epoxy dry bulk materials & protective primer
applications
·
One coat corrosion-inhibitive polyamide epoxy primer,
spray-applied at 2.0 mils nominal DFT
B.
Inorganic Zinc coastal / salt spray environment / primer
application
·
One coat inorganic zinc primer, spray applied at 2.5 mils DFT.
C. Polyamide Epoxy with
Polyurethane Topcoat - prime + best topcoat
·
One coat of polyamide epoxy applied at 2 mils DFT
·
One coat of polyurethane, spray applied to 1.5 mils DFT.
(Standard light colors
include: white, blue, green, gray & tan)
Note: Total coating system
application 3.5 mils DFT
D. MaxCoat DRY-SW
Protection System extreme external protection prime +
intermediate coat + topcoat
·
Prime coat inorganic zinc, spray applied at 2.5 mils DFT.
·
Intermediate coat polyamide epoxy, spray applied at 2 mils DFT.
·
Topcoat polyurethane, spray applied to 1.5 mils DFT.
(Standard light colors
include: white, blue, green, gray & tan)
Note: Total coating system
application 6 mils DFT
TC Coating Spec.
AWWA D100 Section B (continued)
E. No external coating system required
F. Special field applied coating system
to be specified
IV.
Curing & Shipping
·
All coated parts shall be inspected prior to shipment
·
Touch-up paint with instructions shall be included for
application by erection crew |